One-room apartment consumer unit

Price Calc

Project description:

Maximum Power: 11.5 kW

Ingress Protection Code: IP31

Dimentions: 420x335x135, flush-mounted metal distribution iEC TITAN 3

The electrical panel is assembled for an apartment with an area of 32 m². The connection diagram looks like this: The input wires are connected to the electricity meter (not shown in the photo). The meter wire goes to the Circuit Breaker C50, since the maximum switching current of most meters mounted on a DIN rail is 60A. From the Circuit Breaker, the wires go to the input switch, rated up to 63A. After the switch, the wires go to 4 Circuit Breakers C16 (light, bathroom, kitchen and room circuits). There is a residual current switch for the bathroom, Surge Protection Relay and Residual Current Devices are provided for the kitchen and room. Installation connections are made with a flexible cable with a conductor cross-section of 6 mm². For the correct operation of protective devices, a Neutral bus (blue) is used, and a Protective Earth bus (yellow) is also provided for human protection.



This assembly was made for commercial purposes.